@article{oai:miyazaki-u.repo.nii.ac.jp:00005668, author = {藤澤, 一平 and Fujisawa, Ippei and 土屋, 佑太 and Tsuchiya, Yuta and 迫田, 達也 and Sakoda, Tatsuya and 林, 則行 and Hayashi, Noriyuki and 藤澤, 一平 and Fujisawa, Ippei and 土屋, 佑太 and Tsuchiya, Yuta}, journal = {宮崎大学工学部紀要, Memoirs of Faculty of Engineering, University of Miyazaki}, month = {Jul}, note = {Co-generation system has become an effective method to solve the global warming and energy problem. The system can achieve high efficiency both by using electric generation and by exhaust heat recovery. On the other hand, the development of the environmental improvement technology in a greenhouse is demanded agricultural sector. It is thought that desiccant air conditioning system can solve these problems. In this paper, it was purpose to establish system operating conditions according to the outside air and the environment in the greenhouse. For this purpose, dehumidification tests in the greenhouse were conducted at different amount of air to establish system operating conditions according to the outside air and the environment in the greenhouse, and characteristics of the dehumidification quantity on different amount of air and temperature of reproduction air was requested by numerical simulation. Finally, it was conducted whether the environment in the greenhouse could be controlled to the target temperature and humidity in various conditions. As the result, it was confirmed increase in amount of air and rise in reproduction temperature was effective for increasing the dehumidification amount. Moreover, conditions of OA to be controlled was confirmed.}, pages = {137--142}, title = {デシカント空調システムにおける運転条件と除湿性能の関係}, volume = {47}, year = {2018}, yomi = {フジサワ, イッペイ and ツチヤ, ユウタ and サコダ, タツヤ and ハヤシ, ノリユキ and フジサワ, イッペイ and ツチヤ, ユウタ} }